title: Rittal CMC-III LCP: Air In and Temperature
agents: snmp
catalog: hw/environment/rittal
license: GPL
distribution: check_mk
description:
 Note: This check is obsolete, the individual temperatures (top, middle, bottom) are
   also available through the cmciii.temp_in_out check.
 This check monitors the temperature of the inflowing air of
 Rittal CMC-III LCP devices. Temperatures at top, middle and bottom
 of the device are captured, as well as the average value given
 by the device.
 Limits are configured in the Rittal device itself but can be overridden.
 The state given by the Rittal device is taken as the state of the check as follows:
 If the Rittal device returns {OK}, the check is {OK}. Otherwise
 the check is {CRIT}.
 Furthermore, the lower and upper warning and critical limits configured
 in the device are extracted and used as limits for the
 average temperature read from the device.

item:
 None

perfdata:
 One variable: the average temperature in degrees celsius

inventory:
 None